![BENSHAW RSi GM2 Series Скачать руководство пользователя страница 251](http://html1.mh-extra.com/html/benshaw/rsi-gm2-series/rsi-gm2-series_instruction-manual_2735262251.webp)
241
Troubleshooting
890054-00-00
GM2 Series VFD
Keypad
Display
Name
Type
Description
Fan Trip
Latch
Error is detected in the cooling fan with Pr.79 set to 0.
Pre-PID Fail
Latch
The pre-PID functions set with AP.34 ~ AP.36 remain out
of range (% and time) based on the PID feedback signal.
It is treated as a load fault.
Ext-Brake
Latch
When controlling an external (electro-mechanical) brake,
the inverter output current (Brake Release Current)
remained below the value set at Ad.41. Related
parameter OU.31 or OU.33 set to 35 (BR Control) to
control the relay.
Overheat Pre
Alarm
Latch
Inverter Overheat. The inverter temperature exceeded
the temperature set in Pr.77. Related parameters Pr.78
set to 2: Free-Run or 3: Dec. OU.31 or OU.33 set to 41
(Pre Overheat).
Protection Functions Related to Communication Options
Keypad
Display
Name
Type
Description
Lost Command
Level
Lost analog or communications frequency reference.
Based on Pr.12 ~ Pr.15 settings. Related parameters
OU.31 or OU.33 set to 13 (Lost Command).
IO Board Trip
Latch
Displayed when the I/O board or external communication
card is not connected to the inverter or there is a bad
connection.
Displayed when the hold error code continues for more
than 5 sec.
(‘Errc’ -> ’-rrc’ -> ‘E-rc’ -> ’Er-c’ -> ‘Err-‘ -> ’- -rc’ -> ‘Er- -‘ -
> ’- - - -‘ -> ’Errc’ -> …)
Option Trip-1
Latch
Communication error is detected between the inverter
and the installed communication board.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...