Learning Advanced Features
890054-00-00
GM2 Series VFD
141
Multi-function (digital) relay On/Off Control
This feature operates an output relay (Relay1 or Relay2) based on the analog input level.
Set the On level (Ad.67) to activate the relay and the Off level (Ad.68) to de-activate the
relay.
Group Code
Name
Setting
Setting Range
Unit
Ad
66
Output terminal on/off
control mode
1
V1
-
-
67 Output contact On level 90.00
Output contact off level
–
100.00%
%
68 Output contact Off level 10.00
0.00
–
Output terminal on
level
%
OU
31
Multi-function (digital)
relay1 item
34 On/Off
-
-
33
Multi-function (digital)
relay2 item
Multi-function (digital) relay
On/Off
Control Setting Details
Code and Features
Description
Ad.66 On/Off Ctrl Src Select the analog input to use for On/Off control.
Ad.67 On-C Level,
Ad.68 Off-C Level
Set the On and Off levels for the output relay.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...