243
Troubleshooting
890054-00-00
GM2 Series VFD
Troubleshooting Faults
When a fault or warning occurs, refer to the following table for possible causes and remedies.
Items
Cause
Remedy
The load is greater than the
motor’s rated capacity.
Replace the motor and/or inverter with larger
models.
Pr.21 value for the overload trip
level is too low.
Increase the value for the overload trip level.
There is a motor-load connection
problem.
Check connections, measure amps to motor.
Inverter/motor too large for application. Replace the
motor and/or inverter with models with lower
capacity.
Pr.29, Pr.30 underload level is
less than the system’s minimum
load.
Reduce the value for the underload levels.
Acc/Dec time is too short,
compared to load inertia (GD2).
Increase Acc/Dec time.
The load is greater than the
inverter rated capacity.
Replace the inverter with a larger model.
The inverter supplied an output
while the motor was tuning.
Operate the inverter after the motor has stopped or
use the speed search function (Cn.70).
The mechanical brake of the
motor is operating too fast.
Check the mechanical brake.
A ground fault has occurred in
the inverter output wiring.
Check the output wiring.
The motor insulation is damaged. Check/Replace the motor.
Deceleration time is too short for
the load inertia (GD2).
Increase the deceleration time.
Load is regenerative.
Use dynamic braking.
The input voltage is too high.
Check supply voltage. Check DC Link voltage.
Ground fault in the output wiring.
Check the output wiring.
The motor insulation is damaged. Check/Replace the motor.
The input voltage is too low.
Check supply voltage. Check DC Link voltage.
Other equipment connected to
the same power source (e.g., a
welder, direct motor connection,
etc.).
Increase source power capacity.
The input contactor connecting
the power source has a faulty
connection.
Check/Replace the contactor.
The input voltage has decreased
during operation.
Determine if the input voltage is lower than the
specified value.
An input open-phase has
occurred.
Check the input wiring.
The input contactor connecting
the power source has a faulty
connection.
Check/Replace the contactor.
A ground fault has occurred in
the inverter output wiring.
Check output wiring.
The motor insulation is damaged. Check/Replace the motor.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...