Learning Advanced Features
132
890054-00-00
GM2 Series VFD
Auto Restart Setting Details
Code and
Features
Description
Pr.08 RST Restart,
Pr.09 Retry
Number,
Pr.10 Retry Delay
Operates when Pr.08 (RST Restart) is set to 1 (Yes). The number of
auto restart attempts is set at Pr.09 (Restart Number). If a fault occurs
during operation, the inverter automatically resets the fault and
restarts after the set time programmed at Pr.10 (Retry Delay). At each
restart, the inverter decreases the number of Retry attempts. Once the
retry number count reaches 0, the inverter does not attempt any
more automatic restarts. After an auto reset/restart, it will increase the
number of allowable restarts every 60 secs. up to the Pr.09 setting.
At auto restart, the acceleration options are identical to those of
speed search operation. Codes Cn.72~75 can be set based on the
load. Information about the speed search function can be found at
5.13
[Example of auto restart with a setting of 2]
When auto reset/restart is enabled (Pr.08, RST Restart), the inverter will reset from a fault
and automatically start to rotate.