74
GM2 Series VFD
890054-00-00
Learning Basic Features
Stopping the Acc/Dec Operation
Configures a digital input terminal to stop acceleration or deceleration and operate the inverter at
a fixed frequency.
Group Code
Name
Setting
Setting Range
Unit
In
65~69 Px terminal
25
XCEL Stop
0
–
52
-
V/F Control
Configure the inverter’s output voltages, gradient levels and output patterns to achieve a target
output frequency with V/F control. The amount of torque boost used during low frequency
operations can also be adjusted.
Linear V/F Pattern Operation
A linear V/F pattern (also refered to as scaler V/Hz.) configures the inverter output voltage and
frequency to increase or decrease at a fixed rate throughout the speed range. This V/F
characteristic is refered to as a constant V/F ratio (or V/Hz.) and is applied to loads that require
constant torque regardless of the speed.
Group Code
Name
Setting
Setting Range
Unit
dr
09 Control mode
0
V/F
0
–
4
-
18 Base frequency 60.00
30.00
–
400.00
Hz
19 Start frequency 0.50
0.01
–
10.00
Hz
bA
07 V/F pattern
0
Linear
0
–
3
-
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...