Technical Specification
890054-00-00
254
GM2 Series VFD
RSI-XXX-GM2.4C
001
002
003
005
007
010
015
480V,
3
φ
Input
Normal
Duty,
120%
OL
HP
1
2
3
5
7.5
10
15
kW
0.75
1.5
2.2
4
5.5
7.5
11
Amps
2
3.1
5.1
6.9
10
16
23
KVA
1.5
2.4
3.9
5.3
7.6
12.2
17.5
Heavy
Duty,
150%
OL
HP
0.5
1
2
3
5
7.5
10
kW
0.4
0.75
1.5
2.2
4
5.5
7.5
Amps
1.3
2.5
4
5.5
9
12
16
KVA
1
1.9
3
4.2
6.5
9.1
12.2
480V,
1
φ
Input
Normal
Duty
HP
0.5
0.75
1~1.5
2
3
5
7.5
Amps
1.3
1.9
2.8
3.6
5.4
8.7
12.6
Heavy
Duty
HP
-
0.5
1
1.5
3
3
5
Amps
0.7
1.4
2.1
2.8
4.9
6.4
8.7
Output frequency 0
–400 Hz. (IM Sensorless: 0–120 Hz)
Output voltage (V) 3-phase 380
–480 V
Rated
input
Voltage (V)
3-phase 380
–480 VAC (-15% to +10%)
1-phase 480VAC (-5% to +10%)
Input frequency
3-phase 50
–60 Hz (
5%)
1-phase 60Hz (
5%)) only.
Rated
current
(A)
Normal
Duty
2
3.3
5.5
7.5
10.8
17.5
25.4
Heavy
Duty
1.1
2.4
4.2
5.9
9.8
12.9
17.5
Weight (lb /kg)
lbs
2.3
2.4
3.2
3.2
4.4
7.1
7.2
kg
1.04
1.08
1.44
1.46
1.98
3.24
3.28
Heat Dissipation (W)
24
42
71
99
176
231
315
Degree of Protection
IP20, UL Open (UL Type 1 achieved with optional conduit
box)
• The standard motor capacity is based on a standard 4-pole motor.
• The KVA rating is based on a 440V supply voltage for 480V inverters.
• The rated output current is limited based on the carrier frequency set at Cn.04.
• The output voltage is reducued 20%~40% during no-load operations to protect the
inverter from faults, 1 HP ~ 7.5 HP (0.4 ~ 4.0 kW) only.
480 V, 1 HP ~ 15 HP (0.75 kW ~ 11 kW)
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...