Description
1
KEB-1
When the input power is disconnected, it charges
the DC link with regenerated energy. When the
input power is restored, the inverter changes to
normal operation from the KEB-1 energy buffering
operation. The acceeration time set in Cn.83 (KEB
Acc Time) is applied when restoring to normal
operation.
2
KEB-2
When the input power is disconnected, it charges
the DC link with regenerated energy. When the
input power is restored, it changes from the KEB-2
energy buffering operation to the deceleration
stop operation. The decel time set in the dEC
parameter of the operations group is applied
during the deceleration stop operation.
[KEB-1]
CON-78
Px(FX)
DC Link
CON-79
(CON-89)
KEB
[KEB-2]
CON-78
Px(FX)
DC Link
CON-79
KEB
(DRV-04)
Cn.78 KEB Start
Lev,
Cn.79 KEB Stop
Lev
Sets the start and stop points of the kinetic energy buffering operation.
The set values must be based on the low voltage trip level as 100% and
the stop level (Cn.79) must be set higher than the start level (Cn.78).
DC Link
voltage
Output
frequency
Start
frequency
Operation
restore
(Cn.89)
KEB control
DC Link
voltage
Output
frequency
Deceleration
stop
(dEC)
KEB control
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...