RS-485 Communication Features
890054-00-00
GM2 Series VFD
184
Command Loss Protective Operation
Configure the command loss decision standards and protective operations run when a
communication problem lasts for a specified period of time.
Command Loss Protective Operation Setting Details
Code and
Features
Description
Pr.12 Lost Cmd
Mode,
Pr.13 Lost Cmd
Time
Select the operation to (1) Free-Run when a communication error has occurred
and has exceeded the time set at Pr.13.
Configuration
Function
0
None
The reference frequency immediately becomes
the operating frequency without any protection
function.
1
Free-
Run
The inverter blocks output. The motor performs in
free-run condition.
2
Dec
The motor decelerates and then stops.
3
Hold
Input
The inverter continues in the reference frequency
input before the loss of speed.
4
Hold
Output
The inverter continues in the operating frequency
before the loss of speed.
5
Lost
Preset
The inverter operates at the frequency set at Pr.
14 (Lost Preset F).
Setting Virtual Multi-function (digital) Input
Multi-function (digital) inputs can be controlled using a communication address (0h0385). Set
codes CM.70 ~ 77 to the functions to operate, and then set the BIT relevant to the function to 1 at
0h0322 to operate it. Virtual multi-function (digital) inputs operate independently from In.65
–
69
digital multi-function (digital) inputs and cannot be set redundantly. Virtual multi-function (digital)
inputs can be monitored using CM.86 (Virt Dl Status). Before you configure the virtual multi-
function (digital) inputs, set the DRV code according to the command source.
Group Code
Name
Setting
Setting Range
Unit
CM
70
–
77
Communication multi-function
(digital) input x
0
None
0
–
49
-
86
Communication multi-function
(digital) input monitoring
-
-
-
-
Example
: When sending an Fx command by controlling virtual multi-function (digital) input in the
common area via Int485, set CM.70 to FX. Then, assign a 0h0001 value to the communication
address 0h0322 to operate the forward direction operation (Fx) feature.
NOTE:
The following are values and functions that are applied to address 0h0322:
Setting
Function
0h0001
Forward operation (Fx)
0h0003
Reverse operation (Rx)
0h0000
Stop
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...