86
GM2 Series VFD
890054-00-00
Learning Basic Features
Frequency Jump
Use frequency jump to avoid mechanical resonance frequencies. Jump through up to three
frequency bands during acceleration and deceleration. Reference frequencies cannot be set within
the pre-set jump frequency band.
When the reference frequency is increased it will be maintained at the lower limit of a jump
frequency band. As the reference frequency continues to increase and exceeds the range of a jump
frequency band, it will jump to the upper limit of the jump frequency band. Decreasing reference
frequencies operate in the same manner, jumping from upper limit to lower limit. Jump frequencies
apply to all reference frequency sources (voltage, current, RS-485 communication, keypad setting).
Group Code
Name
Setting
Setting Range
Unit
Ad
27 Frequency jump 0
No
0
–
1
-
28
Jump frequency
lower limit 1
10.00
0.00
–
Jump frequency upper limit
1
Hz
29
Jump frequency
upper limit 1
15.00
Jump frequency lower limit 1
–
Maximum frequency
Hz
30
Jump frequency
lower limit 2
20.00
0.00
–
Jump frequency upper limit
2
Hz
31
Jump frequency
upper limit 2
25.00
Jump frequency lower limit 2
–
Maximum frequency
Hz
32
Jump frequency
lower limit 3
30.00
0.00
–
Jump frequency upper limit
3
Hz
33
Jump frequency
upper limit 3
35.00
Jump frequency lower limit 3
–
Maximum frequency
Hz
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...