233
Table of Functions
890054-00-00
GM2 Series VFD
Protection Function G
roup (PAR→Pr
)
Code
Comm.
Address
Name
Setting Range
Initial
Value
Property*
V/F SL
Ref.
Pr.00
-
Jump Code
1
–99
40
O
O
O
Pr.04
0h1B04
Load level
setting
0
Normal Duty
0:Normal
Duty
X
O
O
1
Heavy Duty
Pr.05
0h1B05
Input/output
open-phase
protection
bit
00
–11
00
[1]
X
O
O
1
Output open
phase
10
Input open
phase
Pr.06
0h1B06
Input voltage
range during
open-phase
1
–100 (V)
15
X
O
O
Pr.07
0h1B07
Deceleration
time at fault
0.0
–600.0 (s)
3
O
O
O
Pr.08
0h1B08
Selection of
startup on
trip reset
0 No
0: No
O
O
O
1 Yes
Pr.09
0h1B09
Number of
automatic
restarts
0
–10
0
O
O
O
Pr.10
2
0h1B0A
Automatic
restart delay
time
0.0
–60.0 (s)
1
O
O
O
Pr.12
0h1B0C
Motion at
reference
frequency
loss
0
None
0: None
O
O
O
1
Free-Run
2
Dec
3
Hold Input
4
Hold Output
5
Lost Preset
Pr.13
3
0h1B0D
Time to
determine
reference
frequency
loss
0.0
–120.0 (s)
1
O
O
O
Pr.14
3
0h1B0E
Operating
frequency at
reference
frequency
loss
0, Start frequency
–
Maximum frequency(Hz)
0
O
O
O
Pr.15
3
0h1B0F
Analog input
loss decision
level
0
Half of x1
0: Half of
x1
O
O
O
1
Below x1
Pr.17
0h1B11
Overload
warning
selection
0
No
0: No
O
O
O
1
Yes
Pr.18
0h1B12
Overload
warning
level
30
–180 (%)
110
O
O
O
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...