Installation Considerations
Inverters are composed of various precision electronic devices and the installation environment can
significantly impact the lifespan and reliability of the product. The table below details the ideal
installation and operating conditions for the inverter.
Items
Description
Ambient
temperature*
Normal Duty: 14°F ~ 104°F (-10~40
℃
)
Heavy Duty: 14°F ~ 122°F (-10~50
℃
)
Ambient
humidity
Less than 95% relative humidity (no condensation)
Storage
temperature
-4°F ~ 149°F (-20~65°C)
Environmental
factors
An environment free from corrosive or flammable gases, oil residue, and
dust
Operating
altitude
Vibration
Lower than 3,280 ft (1,000 m) above sea level
(Apply derating of 1% on voltage/output current for every 328 ft. (100m)
above 3,280 ft. (1,000 m), maximum of 13123 ft. (4,000m).
Less than 1G (9.8 m/sec
2
)
Air Pressure
70
–
106 kPa
*
The ambient temperature is the temperature measured at a point 2” (5 cm) from the surface of
the inverter.
Do not allow the ambient temperature to exceed the allowable range while operating the
inverter.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...