78
GM2 Series VFD
890054-00-00
Learning Basic Features
Torque Boost
Manual Torque Boost
Manual torque boost enables users to adjust output voltage during motor starting and low speed
operation. This setting improves motor starting properties and increases low speed torque.
Configure manual torque boost for loads that require high starting torque.
Group Code
Name
Setting
Setting Range
Unit
dr
15
Torque boost
mode
0
Manual
0
–
1
-
16
Forward Torque
boost
2.0
0.0
–
15.0
%
17
Reverse torque
boost
2.0
0.0
–
15.0
%
Manual Torque Boost Setting Details
Code and
Features
Description
dr.16
Fwd Boost
Set torque boost for forward operation.
dr.17
Rev Boost
Set torque boost for reverse operation.
Excessive torque boost will result in over-excitation and motor overheating.