International and national certifications
X90 mobile system User's manual V 1.20 - Translation of the original manual
365
7.4.2 Emission requirements
Testing
Test method per
Limit values per
EN 61131-2: Product standard -
Programmable controllers
Emissions related to lines
EN 55011 / EN 55022
EN 55016-2-1
EN 61000-6-4: Generic standard -
Emissions in industrial sectors
EN 61131-2: Product standard -
Programmable controllers
Radiated emissions
EN 55011 / EN 55022
EN 55016-2-3
EN 61000-6-4: Generic standard -
Emissions in industrial sectors
Emissions related to lines
Test method per
EN 55011 / EN 55022 / EN 55016-2-1
Limit values per
EN 61131-2 (Zone B)
Limit values per
EN 61000-6-4
150 kHz to 500 kHz
79 dB (μV)
Quasi-peak value
66 dB (μV)
Mean
150 kHz to 500 kHz
79 dB (μV)
Quasi-peak value
66 dB (μV)
Mean
AC mains connection
150 kHz to 30 MHz
500 kHz to 30 MHz
73 dB (μV)
Quasi-peak value
60 dB (μV)
Mean
500 kHz to 30 MHz
73 dB (μV)
Quasi-peak value
60 dB (μV)
Mean
-
150 kHz to 500 kHz
97 to 87 dB (µV)
53 to 40 dB (µA)
Quasi-peak value
84 to 74 dB (µV)
40 to 30 dB (µA)
Mean
Telecommunications / network connection
150 kHz to 30 MHz
-
500 kHz to 30 MHz
87 dB (µV)
43 dB (µA)
Quasi-peak value
74 dB (µV)
30 dB (µA)
Mean
Radiated emissions
Test method per
EN 55011 / EN 55022 / EN 55016-2-3
Limit values per
EN 61131-2 (Zone B)
Limit values per
EN 61000-6-4
30 MHz to 230 MHz
40 dB (μV/m)
Quasi-peak value
30 MHz to 230 MHz
40 dB (μV/m)
Quasi-peak value
Electric field (measuring distance 10 m)
30 MHz to 1 GHz
230 MHz to 1 GHz
47 dB (μV/m)
Quasi-peak value
230 MHz to 1 GHz
47 dB (μV/m)
Quasi-peak value
-
1 GHz to 3 GHz
1)
76 dB (µV/m)
Peak value
56 dB (µV/m)
Mean
Electric field (measuring distance 3 m)
1 GHz to 6 GHz
1)
-
3 GHz to 6 GHz
1)
80 dB (µV/m)
Peak value
60 dB (µV/m)
Mean
1)
Depends on highest internal frequency