X90 mobile modules
164
X90 mobile system User's manual V 1.20 - Translation of the original manual
5.4.1.5.5.8 AnalogInputScale
Name:
AnalogInputScale01
This register can be used to specify the scale of the 4 analog inputs (
"AnalogInput" on page 161
). If the actual value
is greater than the value configured in this register, the respective register for the analog input (
"AnalogInput" on
page 161
) is limited to the positive maximum (32767).
For example, if ±128 is configured for AnalogInput04, then the 16 bits represent a value range of ±128 g or without
units if the crest factor has been calculated.
Information:
The configured scaling value is always based on a 100 mV/g sensor. Any sensor that has a different
sensor sensitivity must be reflected in the configuration.
Data type
Values
UINT
See the bit structure.
Bit structure:
Bit
Description
Value
Information
0
Invalid
1
±1
2
±2
3
±4
4
±8
5
±16
6
±32
7
±64
8
±128 (bus controller default setting)
0 - 3
Scaling for AnalogInput01
9 to 15
Invalid
4 - 7
Scaling for AnalogInput02
x
For possible values, see AnalogInput01.
8 - 11
Scaling for AnalogInput03
x
For possible values, see AnalogInput01.
12 - 15
Scaling for AnalogInput04
x
For possible values, see AnalogInput01.
5.4.1.5.5.9 AnalogInputScaleRead
Name:
AnalogInputScale01Read
This register can be used to read the scale of the analog inputs (
see "AnalogInput" on page 161
).
Data type
Values
UINT
0 to 65,535