X90 mobile modules
174
X90 mobile system User's manual V 1.20 - Translation of the original manual
RmsRaw
Name:
RmsRaw01 to RmsRaw04
Registers for reading the raw signal RMS value of the respective channel.
RmsRaw is formed from the raw signal of the oscillation acceleration up to the maximum frequency configured in
register
"MaxFrequencyRaw" on page 186
.
Format
Unit
Value on overflow
REAL
mg
256000.0
RmsVelEnvelope
Name:
RmsVelEnvelope01 to RmsVelEnvelope04
Registers for reading the RMS value of the envelope velocity of the respective channel.
RmsVelEnvelope is formed from the envelope signal of the oscillation acceleration from the configured minimum
frequency (
"MinFrequencyEnvelope" on page 187
) to the configured maximum frequency (
"MaxFrequencyEn-
velope" on page 185
).
This characteristic value is only calculated if the EnableVelocityCalculation bit (configuration in register
"Sensor-
Config" on page 158
) is set for the respective channel; otherwise, 0 is output.
Format
Unit
Value on overflow
REAL
mm/s
16777.21
RmsVelRaw
Name:
RmsVelRaw01 to RmsVelRaw04
Registers for reading the velocity RMS value of the respective channel.
RmsVelRaw is formed from the raw signal of the oscillation velocity from the configured minimum frequency (
"Min-
FrequencyRaw" on page 188
) to the configured maximum frequency (
"MaxFrequencyRaw" on page 186
).
This characteristic value is only calculated if the EnableVelocityCalculation bit (configuration in register
"Sensor-
Config" on page 158
) is set for the respective channel; otherwise, 0 is output.
Format
Unit
Value on overflow
REAL
mm/s
16777.21