International and national certifications
364
X90 mobile system User's manual V 1.20 - Translation of the original manual
Voltage dips
Test method per
EN 61000-4-11
Test values per
EN 61131-2 / Zone B
Test values per
EN 61000-6-2
0% residual voltage
250/300 periods (50/60 Hz)
1)
20 attempts
Criteria C
40% residual voltage
10/12 periods (50/60 Hz)
1)
20 attempts
Criteria C
AC power inputs
70% residual voltage
25/30 periods (50/60 Hz)
1)
20 attempts
Criteria C
1)
Mains frequency per manufacturer data
Short-term interruptions
Test method per
EN 61000-4-11 / EN 61000-4-29
Test values per
EN 61131-2 / Zone B
Test values per
EN 61000-6-2
AC power inputs
0% residual voltage
0.5 periods (50/60 Hz)
1)
20 interruptions
Criteria A
0% residual voltage
1 period (50/60 Hz)
1)
3 interruptions
Criteria B
DC power inputs
0% residual voltage
≥10 ms (PS2)
20 interruptions
Criteria A
-
1)
Mains frequency per manufacturer data
Voltage fluctuations
Test method per
EN 61000-4-11 / EN 61000-4-29
Test values per
EN 61131-2 / Zone B
AC power inputs
-15% / +10%
Test duration per 30 minutes
Criteria A
DC power inputs
-15% / +20%
Each test duration 30 min.
Criteria A