5.4.1.5.4 General registers
5.4.1.5.4.1 ActSpeed
Name:
ActSpeed01 to ActSpeed04
Registers for the current speed for calculating frequency bands 01 to 32 if they have been configured as speed-
dependent.
The current speed must be specified in 1/100 Hz. Automation Runtime handles this.
If the 4 different speed data points are not sufficient, e.g. for several different gear ratios, the speed ratio can also be
included when calculating the standardized damage frequency for the frequency band (
"FrequencyBandDmgFre-
q60rpm" on page 195
register).
Format
Values
Unit
REAL
0 to 655.35
1)
in 1 Hz
1)
The driver reduces larger values to 655.35.
5.4.1.5.4.2 AutogainDelay
Name:
AutogainDelay01
This register can be used to configure the autogain delay for all 4 channels.
To ensure that even smaller signals can be calculated precisely, the autogain can be increased in steps. This
happens if there has been no overflow in the number of measurement cycles configured in this register and all
conditions for the next step were always met. If an overflow does occur, then autogain is reduced immediately
by one step.
The unit for delaying autogain is specified in measurement cycles (300 ms).
Data type
Values
Information
UINT
1 to 65,535
Number of measurement cycles.
Bus controller default setting: 50
5.4.1.5.4.3 AutogainDelayRead
Name:
AutogainDelay01Read
Register for reading the current
"AutogainDelay" on page 156
configuration.
Data type
Values
UINT
0 to 65,535