498 Fault tracing
BA96 FSO out of SDI
SDI positive or SDI
negative exceeded the
tolerance limit to the
forbidden direction.
Make sure that SDI tolerance values
are defined properly.
Check limits of the drive. For
example, see the usage of DC hold
from the drive firmware manual.
BA99 FSO passivated
FSO module was
passivated due to safety
fieldbus problems.
Check the fieldbus connection and
fieldbus controller for passivation
cause.
5)
BAA1 FSO STO request FSO module received an
external STO request.
-
1)
BAA2 FSO SSE request FSO module received an
external SSE request.
-
1)
BAA3 FSO SS1 request
FSO module received an
external SS1 request.
-
1)
BAA4 FSO SLS1 hit
FSO module detected an
SLS1 speed trip limit
violation.
Investigate the reason for trip from
the application point of view. If
application is OK, then make sure
that SLS is configured properly.
Make sure that SLS trip limits are
defined properly.
Check that transient mute time values
are defined properly (
or
if enabled, and
2) 6)
BAA5 FSO SLS2 hit
FSO module detected an
SLS2 speed trip limit
violation.
Investigate the reason for trip from
the application point of view. If
application is OK, then make sure
that SLS is configured properly.
Make sure that SLS trip limits are
defined properly.
Check that transient mute time values
are defined properly (
or
if enabled, and
2) 6)
BAA6 FSO SLS3 hit
FSO module detected an
SLS3 speed trip limit
violation.
Investigate the reason for trip from
the application point of view. If
application is OK, then make sure
that SLS is configured properly.
Make sure that SLS trip limits are
defined properly.
Check that transient mute time values
are defined properly (
or
if enabled, and
2) 6)
Code
(hex)
Name
Cause
What to do
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...