Parameters 427
SLSx.23 SLS2 trip limit
positive
Sets the SLS2 positive speed limit that trips
the drive.
0.0 rpm
0.0…35880.0 rpm
Speed
SLSx.24 SLS2 output
Sets the digital output for SLS2 function.
Active when SLS2 function is active and the
motor speed is below the SLS2 limit (that is,
when the SLS2 monitoring is on).
None
No output connected
DO X113:7 & X114:7 Redundant output X113:7 & X114:7
DO X113:8 & X114:8 Redundant output X113:8 & X114:8
DO X113:9 & X114:9 Redundant output X113:9 & X114:9
DO X113:7
Single output X113:7
DO X113:8
Single output X113:8
DO X113:9
Single output X113:9
DO X114:7
Single output X114:7
DO X114:8
Single output X114:8
DO X114:9
Single output X114:9
SLSx.27 Mute time for SLS2 Sets the SLS2 specific mute time for limit hit
situations.
This parameter is effective only with the safe
speed estimate.
0 ms
0…10000 ms
SLSx.31 SLS3 input
Sets the digital input for the SLS3 function.
None
No input connected
DI X113:1 & X114:1 Redundant input X113:1 & X114:1
DI X113:2 & X114:2 Redundant input X113:2 & X114:2
DI X113:3 & X114:3 Redundant input X113:3 & X114:3
DI X113:4 & X114:4 Redundant input X113:4 & X114:4
DI X113:1
Single input X113:1
DI X113:2
Single input X113:2
DI X113:3
Single input X113:3
DI X113:4
Single input X113:4
DI X114:1
Single input X114:1
DI X114:2
Single input X114:2
DI X114:3
Single input X114:3
DI X114:4
Single input X114:4
SLSx.32 SLS3 trip limit
negative
SLS3 negative speed limit that trips the
drive.
0.0 rpm
-35880.0 …0.0 rpm Speed
SLSx.33 SLS3 trip limit
positive
Sets the SLS3 positive speed limit that trips
the drive.
0.0 rpm
0.0…35880.0 rpm
Speed
Index
Name/Value
Description
Factory
default
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...