208 PROFIsafe
Unsig
ned16
(used
as
bits)
2
0
Variable_SLS_req
uest
Variable SLS (Safely-limited speed) activation
requested by the controller and Variable SLS limit is
valid.
1
Reserved
*)
Must not be used (must be 0).
2
SF_end_ack
Safety function ending acknowledgement = 1,
no acknowledgement = 0.
3
Reserved
*)
Must not be used (must be 0).
4
SSM4_activate
SSM4 (Safe speed monitor) activation requested by
the controller.
5
SSM3_activate
SSM3 (Safe speed monitor) activation requested by
the controller.
6
SSM2_activate
SSM2 (Safe speed monitor) activation requested by
the controller.
7
SSM1_activate
SSM1 (Safe speed monitor) activation requested by
the controller.
Unsig
ned16
(used
as
bits)
3
0
Safe_output_X114
_9_ctrl
State of the safe output X114:9 (see section
on page
). 1 = 24 V, 0 = 0 V.
1
Safe_output_X114
_8_ctrl
State of the safe output X114:8 (see section
on page
). 1 = 24 V, 0 = 0 V.
2
Safe_output_X114
_7_ctrl
State of the safe output X114:7 (see section
on page
). 1 = 24 V, 0 = 0 V.
3
Safe_output_X113
_9_ctrl
State of the safe output X113:9 (see section
on page
). 1 = 24 V, 0 = 0 V.
4
Safe_output_X113
_8_ctrl
State of the safe output X113:8 (see section
on page
). 1 = 24 V, 0 = 0 V.
5
Safe_output_x113
_7_ctrl
State of the safe output X113:7 (see section
on page
). 1 = 24 V, 0 = 0 V.
6
Negative_Scaling
Selects whether Variable SLS limit is scaled for
negative direction. 0 = Limit scaled, 1 = Limit not
scaled (100%).
7
Positive_Scaling
Selects whether Variable SLS limit is scaled for
positive direction. 0 = Limit scaled, 1 = Limit not
scaled (100%).
Intege
r16
4
Variable_SLS_limit
_MSB
Safely-limited speed relative limit (MSB) [0.01%]
Intege
r16
5
Variable_SLS_limit
_LSB
Safely-limited speed relative limit (LSB) [0.01%]
*)
If the PROFIsafe message includes a safety function request which is not supported or if the
safety function has not been configured, the FSO module activates the SSE function and
generates an FSO configuration fault (see chapter
Type
Octet Bit Name
Description
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...