284 PROFIsafe
Typical communication errors
This table lists some typical error situations in the PROFINET and PROFIsafe
communication.
68
(0x0044)
Parameter "F_SIL" exceeds SIL from
specific device application.
F_SIL defined for this device at F-Host is
not correct. This device supports only
F_SIL = 3.
69
(0x0045)
Parameter "F_CRC_Length" does not
match the generated values.
F-Parameter checksum length different
from 3 octets. This device supports only
three (3) octet CRC2.
70
(0x0046)
Parameter "F_Par_Version" set
incorrectly.
Version of F-Parameter defined for this
device at F-Host is not correct. This device
supports only V2.
71
(0x0047)
CRC1 Fault
Checksum CRC1
calculated over the
F-Parameters does not match the
checksum value in the F-Parameters.
72
(0x0048)
Device-specific diagnosis information
Unsupported PROFINET submodule
identification number received from the
controller station upon PROFINET
connection, or general error in the F-
Parameters.
Fault
Cause
What to do
You cannot start
the PROFINET
communication.
The FB module station name
saved in the FB module does not
match the station name of the FB
module in the PLC configuration.
Check the station names in both
places.
The FB module IP address saved
in the FB module does not match
the IP address of the FB module in
the PLC configuration.
Check the IP settings in both places.
The FB module is not configured
for the PROFINET
communication.
Check drive parameter
51.01
or
54.01
. See the FB module user’s
manual for details.
Value
(hex)
Description
Notes
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...