Safety functions 173
Variable SLS with time monitoring
In Variable SLS with time monitoring, the ramp according to which the drive
decelerates the motor to different speeds is monitored using the time monitoring
method.
Drive parameters define the deceleration ramp. If the motor speed is
accelerated, drive parameters define the acceleration ramp and it is not monitored.
For configuration, see section
How to configure Variable SLS with time monitoring
page
A
Variable SLS trip limits (parameter
and the scaling values set in the safety PLC)
B
SLS time delay (parameter
): Delay for forcing to start SLS monitoring.
C
Response time (depends on system configuration, see page
Variable SLS trip limit (A)
Step
Description
1
The Variable SLS request is received from the safety PLC (for example, 70%). The
FSO sends a request to the drive to ramp down the motor speed to the new SLS speed
limit. The FSO start a counter for the SLS time delay (B).
2
After time C has elapsed, the drive starts to ramp down the motor speed.
The drive
(parameter
23.13
or
23.15
) defines the deceleration ramp.
The FSO starts the SLS monitoring when the motor speed is in the middle of the new
SLS limit and the SLS trip limit (see also section
How to configure mute time for
on page
3
The new motor speed has been reached. The Variable SLS active indication
(parameter
) goes on.
4
The FSO starts the SLS monitoring at the latest here, that is, after the SLS time delay
(B) has elapsed.
Note
: If the motor speed is above the SLS trip limit after the SLS time delay (B) has
elapsed, the FSO module activates the SSE function. For more information, see
section
SLS with time monitoring and speed above monitored speed
on page
.
varSLS status
& indication
C
2
5
varSLS request
4
B
Motor speed
Time
6
7
8 9 10
11 12
B
A
C
C
A
A
3
1
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...