![ABB FSO-21 Скачать руководство пользователя страница 472](http://html.mh-extra.com/html/abb/fso-21/fso-21_user-manual_2728472.webp)
472 Verification and validation
OR
b) With time monitoring:
-
= Time
-
Indication:
•
•
•
3. If you made any changes, download and validate the configuration with the Drive
composer pro PC tool.
4. Make sure that you can run and stop the motor freely. Start the drive and
accelerate the motor to the maximum speed of the application.
5. Activate the SSE function. For example, press the emergency stop button which
is wired to FSO module input for the SSE function.
6. Remove the SSE function user request.
7. a) If manual acknowledgement (or safebus acknowledgement) is in use: Verify by
trying to acknowledge the function, that it is not possible before the motor speed
is low enough:
•
.
•
With safety encoder:
b) If automatic acknowledgement is in use: Verify that the function is not
acknowledged before the motor is in safe state, see the conditions above.
8. Make sure that the motor speed decelerates as expected and the FSO does not
trip to the monitoring limit (ramp or time).
9. Start the drive and accelerate the motor to the maximum speed of the application.
10. Activate the SSE function. For example, press the emergency stop button which
is wired to the FSO module input for the SSE function.
11. Remove the SSE function user request.
12. Activate the coast stop of the drive.
You can, for example, cause an external fault trip in the drive. For more
information, see the drive firmware manual (Group
31 Fault functions
).
13. Make sure that the FSO trips the drive, and activates the STO function according
to the application requirements.
14. Make sure that the acknowledgement of the STO function is not possible before
the motor is in safe state
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...