Configuration 393
Configuring mute times
WARNING!
The mute time increases the response time of the safety system.
This must be considered in the design of the safety system.
To minimize the effects of small transient variations in the speed measurement data,
you can fine-tune the operation of the safety functions with mute time parameters. For
the description of this feature, see
on page
How to determine values for mute time parameters
The suitable values for mute times can be determined by monitoring FSO speed
signals (
,
) with the Drive composer
pro tool. If possible, all transient situations within the whole speed range of the
application should be monitored. Based on the results, the mute times should be set
as short as possible. After the mute time parameters have been correctly set, safety
functions can be validated. You can check the motor speed for motor control from the
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...