![ABB FSO-21 Скачать руководство пользователя страница 245](http://html.mh-extra.com/html/abb/fso-21/fso-21_user-manual_2728245.webp)
PROFIsafe 245
These two define the codename for the PROFIsafe relationship of this
particular FENA module and the safety controller station.
•
F_WD_Time is the PROFIsafe watchdog time. See section
on page
for instructions on how to calculate the correct
watchdog time.
•
On the
PNIO Module Safety I/O Mapping
tab, type names for the variables
that refer to the PROFIsafe message data in the safety PLC program. (See
section
ABB_PS1 profile F-Output user data
on page
16. Create the configuration data for the controller station:
•
Right-click on the
Application
and select
Create Configuration Data
.
17. Create the safety configuration data for the controller station:
•
Right-click on the
AC500_S
and select
Create Safety Configuration Data
.
18. Download the safety and “non-safety” PLC programs. This is done through
Codesys, by double clicking on "Application". Then in Codesys, open Online drop
down menu and choose Login. Same is done to the safety program by double
clicking on "AC500_S".
Note:
The non-safety program may be empty, but the safety program must contain a
watchdog in order for PROFIsafe to run.
19. Create a program that controls the drive:
•
Double-click the
Application.
This opens the PLC program in the CoDeSys
programming tool.
20. Create a safety program that controls the FSO via PROFIsafe:
•
Double-click the
AC500_S.
This opens the safety PLC program in the
CoDeSys programming tool.
Note
: If you do not have an existing safety program, you must at least implement
watchdog toggling.
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...