PROFIsafe 285
You cannot start
the PROFIsafe
communication.
The drive safety parameters are
not set correctly.
In the ACS880/DCS880 drives, check
the values of parameters
and
. See section
How to configure the safety
communication with PROFIsafe
page
for details.
The PROFIsafe destination
address of the FB module does
not match the station name of the
FB module in the PLC
configuration.
In the ACS880/DCS880 drives, check
the value of parameter
. See section
How to configure the safety
communication with PROFIsafe
page
for details.
PROFIsafe
communication
watchdog time
exceeds often.
The watchdog time is too short.
Calculate a new watchdog time. See
section
on page
.
All errors solved
but you still cannot
start the
PROFIsafe
communication.
After you have modified the
configuration of the safety
devices, you may have to reboot
the whole system before the
changes take effect.
Reboot the safety PLC.
If this does not help, reboot also the
FSO module, the FB module and the
drive.
To reboot the FSO module:
• switch the power off and on, or
• use drive parameter
FSO reboot
(parameter
96.09
, see the drive
firmware manual).
To reboot the FB module:
• switch the power off and on, or
• use drive parameter
FBA A/B PAR
REFRESH
(parameter
51.27/54.27
, see the drive
firmware manual).
To reboot the drive:
• switch the power off and on, or
• use drive parameter
Control board
boot
(parameter
96.08
, see the
drive firmware manual).
Fault
Cause
What to do
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...