PROFIsafe 209
ABB_PS2 profile F-Input user data
This table shows the bit order of the F-Input user data, which is included in the
PROFIsafe message sent from the FSO module to the safety PLC. For all the bits in
the F-Input data, one (1) means active and zero (0) non-active.
Note
: In the Fail-safe and Configuration states, all the bits in the PROFIsafe message
are set to “0”. In these cases, you can read the FSO state from:
• Siemens PLC: bits QBAD and PASS_OUT in the PROFIsafe data block
• ABB PLC: bit Device_Fault in the PROFIsafe data structure.
See also section
on page
Type
Octet Bit Name
Description
Unsig
ned16
(used
as
bits)
0
0
SLS2_active
SLS2 (Safely-limited speed) is active. Active when
the SLS2 function is active and the motor speed is
below the SLS2 limit (that is, when the SLS2
monitoring is on).
1
SLS1_active
SLS1 (Safely-limited speed) is active. Active when
the SLS1 function is active and the motor speed is
below the SLS1 limit (that is, when the SLS1
monitoring is on).
2
Reserved
*)
The value is 0. Must be ignored by the F-Host.
3
Reserved
*)
The value is 0. Must be ignored by the F-Host.
4
SS1_active
SS1 (Safe stop 1) function is active.
5
SSE_active
SSE (Safe stop emergency) function is active.
6
SBC_active
SBC (Safe brake control) function is active.
7
STO_active
STO (Safe torque off) function is active.
Unsig
ned16
(used
as
bits)
1
0
Reserved
*)
The value is 0. Must be ignored by the F-Host.
1
Reserved
*)
The value is 0. Must be ignored by the F-Host.
2
Reserved
*)
The value is 0. Must be ignored by the F-Host.
3
Reserved
*)
The value is 0. Must be ignored by the F-Host.
4
SAR1_active
SAR1 (Safe acceleration range) is active.
5
SAR0_active
SAR0 (Safe acceleration range) is active.
6
SLS4_active
SLS4 (Safely-limited speed) is active. Active when
the SLS4 function is active and the motor speed is
below the SLS4 limit (that is, when the SLS4
monitoring is on).
7
SLS3_active
SLS3 (Safely-limited speed) is active. Active when
the SLS3 function is active and the motor speed is
below the SLS3 limit (that is, when the SLS3
monitoring is on).
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...