Fault tracing 499
BAA7 FSO SLS4 hit
FSO module detected an
SLS4 speed trip limit
violation.
Investigate the reason for trip from
the application point of view. If
application is OK, then make sure
that SLS is configured properly.
Make sure that SLS trip limits are
defined properly.
Check that transient mute time values
are defined properly (
or
if enabled, and
).
2) 6)
BAA8 FSO SMS hit
FSO module detected an
SMS speed trip limit
violation.
Investigate the reason for trip from
the application point of view. If
application is OK, then make sure
that SMS is configured properly.
Make sure that SMS trip limits are
defined properly.
Check that transient mute time values
are defined properly (
or
if enabled).
2) 6)
BAA9 FSO SAR0 hit
FSO module detected an
SAR0 limit violation.
Make sure that the drive can
decelerate the load using the ramp
time (
).
2)
BAAA FSO SAR1 hit
FSO module detected an
SAR1 limit violation.
Make sure that the drive can
decelerate the load using the ramp
time (
).
2)
BAB0 FSO SDI positive
hit
SDI positive exceeded the
tolerance limit to the
forbidden direction.
Make sure that SDI tolerance values
are defined properly.
Check limits of the drive. For
example, see the usage of DC hold
from the drive firmware manual.
2)
BAB1 FSO SDI negative
hit
SDI negative exceeded
the tolerance limit to the
forbidden direction.
Make sure that SDI tolerance values
are defined properly.
Check limits of the drive. For
example, see the usage of DC hold
from the drive firmware manual.
2)
Code
(hex)
Name
Cause
What to do
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...