218 PROFIsafe
Safe (Module
passivation)
The FSO application is running and there has been an error in the
PROFIsafe communication.
The FSO module and, as a result, all its I/O channels are passivated.
Possible reasons for module passivation are:
1. PROFIsafe communication failure (CRC error)
2. PROFIsafe watchdog timeout exceeded.
The drive is stopped using the configured method. In the end, the drive
STO is activated. The fail-safe value “0” is set to all I/O channels.
If the connection to the PROFIsafe F-Host is possible, the fail-safe value
“0” is transferred to the safety PLC for all I/O channels.
If the PROFIsafe communication is broken, the safety application
continuously attempts to establish a communication to the safety PLC.
A state transition to another RUN state is possible only if the detected
error
has been solved.
PROFIsafe Status Byte bits in the F-Host for the FSO module
(if communication is possible):
• OA_Req_S = 0
• FV_activated_S = 1
• Device_Fault = 0
• CE_CRC = 1, in case of a communication error,
CE_CRC = 0, otherwise
• WD_timeout = 1, in case of a watchdog timeout,
WD_timeout = 0, otherwise
ABB_PS1 or ABB_PS2 profile bits in the F-Host for the FSO module:
• FSO_mode.1 = 0
• FSO_mode.0 = 1
• SF_end_ack_req_local = 0
• SF_end_ack_req = 0
• FSO_state = 1
State
Description
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...