Verification and validation 471
5. Activate the SSE function. For example, press the emergency stop button, which
is wired to the FSO input for the SSE function.
6. Make sure that the drive STO is activated immediately after the SSE request.
7. Remove the SSE function user request.
8. a) If manual acknowledgement (or safebus acknowledgement) is in use: Verify by
trying to acknowledge the function, that it is not possible before the motor is in
safe state.
b) If automatic acknowledgement is in use: Make sure that the function is not
acknowledged and that the delays are correctly configured by verifying that the
drive cannot be restarted before the motor is in safe state.
Validation of the SSE with emergency ramp function
1. Make sure that the input for the SSE function is configured according to the wiring
diagram.
2. Make sure that the SSE function and SAR0 setting or time monitoring limit is
configured correctly according to your design. For a configuration example see
section
How to configure SSE with time monitoring
on page
or
configure SSE with ramp monitoring
. Check these settings:
Activation:
•
•
.
•
Note:
activation can also come from the PROFIsafe
Acknowledgement:
•
•
if manual acknowledgement is
used.
Functionality:
•
= Emergency ramp
•
•
200.201 SAR0 ramp time to zero
•
SSE.16 SSE ramp zero speed delay for STO
, if used
•
•
•
a) With ramp monitoring:
-
= Ramp
SARx.02 SAR initial allowed range
SARx.11 SAR0 max ramp time to zero
SARx.12 SAR0 max ramp time to zero
.
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...