![ABB FSO-21 Скачать руководство пользователя страница 201](http://html.mh-extra.com/html/abb/fso-21/fso-21_user-manual_2728201.webp)
PROFIsafe 201
Status Byte and CRC2 bit order
PROFIsafe messages sent from the FSO module to the safety PLC include the
F-Input user data, the Status Byte and CRC2.
This table shows the bit order of the Status Byte and CRC2.
N
i
is the length of F-Input user data.
FSO PROFIsafe profiles
The content of the F-Input and F-Output user data is configured with FSO specific
PROFIsafe profiles. The FSO-21 module supports the ABB_PS1 and
ABB_PS2
profiles.
The ABB_PS1 profile provides the functionality to control and monitor the safety
functions, the SLS limits, the safe speed value and the states of the FSO I/O. In
addition to the functionality in the ABB_PS1 profile, the ABB_PS2 profile includes the
safe position data. The ABB_PS2 profile requires that an encoder is used in the
safety system.
Octet Bit
Name
Description
Status Byte
N
i
7
Reserved
The value is always 0. Must be ignored by the F-Host.
6
cons_nr_R
Vconsnr_d has been reset.
5
Toggle_d
Toggle bit
4
FV_activated
Fail-safe values (FV) activated.
3
WD_timeout
Communication fault: Watchdog timeout
2
CE_CRC
Communication fault: CRC error
1
Device_Fault
Failure exists in the F-Device.
0
iPar_OK
F-Device has new iParameter values assigned.
Not in use. The value is always 0.
CRC2
N
i
+1
7
CRC bit 23
Octet 3 (MSB) of 24 bit CRC
…
0
CRC bit 16
N
i
+2
7
CRC bit 15
Octet 2 of 24 bit CRC
…
0
CRC bit 8
Ni+3
7
CRC bit 7
Octet 1 (LSB) of 24 bit CRC
…
0
CRC bit 0
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...