152 Safety functions
Step Description
1
The SLS request is received. The motor speed is above the SLS trip limit positive (A).
The drive starts to ramp down the motor speed. The SAR1 parameter
defines
the deceleration ramp slope until the speed reaches the SLS limit. The FSO starts the
SAR1 ramp monitoring (parameters
). SAR1 configuration defines
the target and monitoring limits for the deceleration ramp (
,
).
Note:
If parameter
has value 0, the drive (drive parameter 23.23) defines the
ramp.
2
The drive trips on a fault, there is a drive power loss, or user stops the drive by coast
stop. SAR1 monitoring of the FSO is on (parameter
configured as Monitoring
active). As the modulation is lost, FSO's safe speed estimation is stopped and it starts
to use the last speed information that it had before the modulation was lost. With
Monitor active, SAR1 monitoring stays active also when the modulation is lost
from the drive.
delay starts.
3
Modulation of the drive has not returned and the safe speed estimation with the last
valid speed information hits the SAR1 monitoring and FSO activates STO function and
STO indication (parameter
page
for more information on how to configure the STO function.
If the modulation returns before the last valid speed estimation of FSO hits the SAR1
monitoring limit, the drive will continue the deceleration for as long as the speed stays
within the SAR1 ramp monitoring limits.
4
SLS indication goes on after
delay has elapsed.
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...