212 PROFIsafe
Note
: The states of all FSO inputs and outputs are shown in the PROFIsafe
message. These states show also the states of SBC outputs and feedback inputs.
FSO module modes and states
When the FSO module is connected to a safety PLC via the PROFIsafe
communications bus, the FSO module can be in the following modes and states:
• Start-up mode
• Configuration mode
• Fail-safe mode
• RUN states:
•
Operational
•
Safe (User acknowledgement request)
•
Safe (Module passivation)
•
Safe (Module passivation & reintegration)
•
Safe (Module passivation with a command).
The FSO module modes and states are described in the following two figures and
tables.
The first figure shows the modes, states and transitions during normal operation. The
second figure shows the modes, states and transitions when fatal errors in the FSO
module occur or when cycling power of the FSO module.
Note
: If PROFIsafe is not configured, see the FSO states described in section
in chapter
.
Note
: If PROFIsafe is configured, the FSO module stays in the Start-up mode until it
has received valid F-Parameters from the safety PLC.
Intege
r16
6
Safe_speed_MSB
The current motor speed value from the FSO
(MSB).
Intege
r16
7
Safe_speed_LSB
The current motor speed value from the FSO
(LSB).
Intege
r16
8
Safe_position_MSB
Safe position value (MSB).
Intege
r16
9
Safe_position_LSB
Safe position value (LSB).
*)
The safety PLC must ignore the value of the reserved bits. This ensures the compatibility
with future versions of the PROFIsafe profile where the reserved bits may be used.
Type
Octet Bit Name
Description
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...