396 Configuration
this example, SLS1 function is used. Function-specific mute time is set long enough
to prevent the limit hit during acceleration.
• parameter
= Enabled
• parameter
= 1200 ms (function-specific)
This example also applies to:
• Trip limit hits in the SLS2…4 and Variable SLS functions when the SLSx mute
times are enabled with parameter
• Trip limit hit in the SMS function when the SMS mute time (
) is enabled
with parameter
.
- - - Actual speed
Safe speed estimate
SLS1 trip limit positive SLSx.14
1
Amount of slip in safe speed estimate during acceleration
2
Safe speed estimate exceeds the SLS trip limit
3
Safe speed estimate returns below SLS trip limit before the mute time for SLS1 has
elapsed. SSE is not activated and drive continues normal operation.
2
Speed
Time
1
3
SLSx.17
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...