Safety functions 141
user can also set the reaction type and the delay for activating the STO indication
after the modulation loss.
For this procedure to work, at least the auxiliary power (24 V DC) to the control unit
and the FSO module must be on. For more information, see section
when modulation is lost during deceleration ramp, with ramp monitoring
on page
SLS with speed below monitored speed
This applies to both time and ramp monitoring.
A
SLS trip limit positive (parameter
B
,
- - -
SSE coast stop due to SLS trip limit hit
Motor speed
Time
1
3
2
4
A
B
SLS request
SLS monitoring
SLS indication
Manual
acknowledgment
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...