330 Configuration
How to configure the SBC in the SS1 function
Use these parameters to configure the SBC:
1. Set the correct SBC speed limit with parameter
:
•
If the value is zero (
0 rpm
) the SBC is not used in the SS1 and SSE with
emergency ramp functions.
•
If the value is positive (the corresponding negative value is used in the
opposite direction), the FSO activates the SBC and drive STO functions at the
same time when the speed limit is reached. See section
with speed limit activated SBC
2. You can also set a negative delay with parameter
:
•
If the value is negative, the FSO activates the SBC at the speed limit (set with
parameter
) and the drive STO after this delay.
See section
How to configure SS1 with speed limit activated SBC, SBC before
.
•
If the value is zero (
0 ms
) or positive, the FSO activates the SBC and drive
STO functions at the same time when the speed limit is reached.
Note
is
Delayed brake,
the same
parameter
is used also in the STO and SSE with
immediate STO functions (see section
How to configure the SBC in the STO
). In the SS1 (and SSE with emergency ramp) function, this
parameter is relevant always when parameter
not zero.
Monitoring limit hits in the SS1 function
When you configure the SBC in the SS1 (and SSE with emergency ramp) function,
this does not take the SBC into use in the STO function. Therefore, the SBC is not
activated in limit hit situations if parameter
is
None.
For limit
hit situations, you have to configure the SBC also in the STO function. See section
How to configure the SBC in the STO function
How to configure mute time for SBC speed limit detection
on page
.
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...