Configuration 391
How to configure SDI with ramp monitoring
Example:
The figure below shows an example of an SDI positive function with ramp
monitoring set-up:
• Version 1 of SDI functions activated (
=
Version 1
)
• SDI positive function activated (
Enabled
)
• monitored deceleration ramp (
SDI activation monitoring method
=
Ramp
)
• deceleration ramp and monitoring limits according SAR1 parameters (see section
on page
• SDI tolerance into the forbidden direction 2 degrees
=
2 deg
)
• automatic acknowledgement (
Automatic
)
• redundant activation button connected to input
=
DI X113:2 & X114:2
)
• single output connected (
DO X114:7
).
= DI X113:2 &
X114:2
= None
= DO X114:7
= None
= Ramp
= Automatic
= 2 deg
(not shown in the
figure)
SDI positive
Time
Speed
Inputs
Outputs
SDI activated,
SAR1 monitoring started
SDI monitoring started
= Version 1
Remember to configure SAR1!
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...