![ABB FSO-21 Скачать руководство пользователя страница 493](http://html.mh-extra.com/html/abb/fso-21/fso-21_user-manual_2728493.webp)
Fault tracing 493
A7D9 FSO encoderless
fault
Speed estimates differ too
much.
• Check the behavior of the driven
load compared with the drive
control parameter settings.
• Check that the drive is suitable for
the drive train and the motor.
• Adapt control parameters if gear
play or torsional rigidity causes
problems.
4)
A7DA FSO temperature
fault
FSO module temperature
is too high.
• Check ambient conditions. Reboot
the FSO module (switch the power
off and on or use drive parameter
96.09 FSO reboot
, see the drive
firmware manual).
• Make sure that cooling is sufficient.
Contact your local ABB
representative.
4)
A7DB FSO undefined
warning
FSO new version,
undefined warning in the
drive event system.
Contact your local ABB
representative.
AA90 FSO stop
completed
FSO module has
completed the STO, SS1
or SSE function.
-
1)
AA91 FSO safe speed
limit
FSO module detected an
SLS or SMS speed trip
limit violation.
Check the separate code related to
SLS and SMS functions.
See section
for limit hits and special events
on
page
2) 3)
AA92 FSO out of eme
ramp
Motor speed was not
inside the ramp window
during the SSE function.
Make sure that the drive can
decelerate the load using the ramp
time (
).
2)
AA93 FSO ramp
coasted
Drive coasted the motor
to stop instead of using
the ramp.
Check that the FSO module zero
speed limit for the deceleration ramp
is not excessive (
or
).
2)
AA94 FSO out of safe
ramp
Motor speed was not
inside the ramp window
during the SS1 function.
Make sure that the drive can
decelerate the load using the ramp
time (
).
2)
Code
(hex)
Name
Cause
What to do
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...