Verification and validation 473
Validation of the SS1 function
1. Make sure that the input for the SS1 function is configured according to the wiring
diagram.
2. Make sure that the SS1 function, and SAR1 setting or time monitoring limit is
configured correctly according to your design. For a configuration example, see
chapter
How to configure SS1 with time monitoring (SS1-t)
, or
to configure SS1 with ramp monitoring (SS1-r)
on page
. Check these
settings:
Activation:
•
•
.
•
Note:
activation can also come from the PROFIsafe
Acknowledgement:
•
•
if manual acknowledgement is
used.
Functionality:
•
= Version 1
•
SS1-r ramp zero speed delay for STO
(if used)
•
•
•
drive parameter
23.23 emergency stop time
, if
= 0 ms
•
if with safe speed estimation:
•
•
a) If ramp monitoring is in use:
-
= SS1-r
OR
b) If time monitoring is in use:
-
= SS1-t
Indication:
•
•
•
.
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...