222 PROFIsafe
12
Safe (Module
passivation &
reintegration)
Fail-safe
Fatal error(s) (CPU test, RAM test, etc. failed)
detected.
13
Safe (Module
passivation)
Fail-safe
Fatal error(s) (CPU test, RAM test, etc. failed)
detected.
14
Safe (Module
passivation &
reintegration)
Start-up
The FSO module goes to this state by cycling
power of the FSO module or by giving the reset
command via the drive (parameter
96.09 FSO
reboot
, see the drive firmware manual).
15
Start-up
Start-up
The FSO module goes to this state by cycling
power of the FSO module or by giving the reset
command via the drive (parameter
96.09 FSO
reboot
, see the drive firmware manual).
16
Safe (User
acknowledgement
request)
Fail-safe
Fatal error(s) (CPU test, RAM test, etc. failed)
detected.
17
Safe (User
acknowledgement
request)
Start-up
The FSO module goes to this state by cycling
power of the FSO module or by giving the reset
command via the drive (parameter
96.09 FSO
reboot
, see the drive firmware manual).
18
Safe (Module
passivation with a
command)
Safe (Module
passivation)
PROFIsafe watchdog time or PROFIsafe
communication error was detected.
19
Safe (Module
passivation)
Safe (Module
passivation
with a
command)
Module error (watchdog time or communication
error (CRC)) has been solved and command
“activate_FV_C = 1” is received.
20
Safe (User
acknowledgement
request)
Safe (Module
passivation)
PROFIsafe watchdog time or PROFIsafe
communication error was detected.
21
Safe (Module
passivation)
Safe (User
acknowledgem
ent request)
Module error (watchdog time or communication
error (CRC)) has been solved and
• command “activate_FV_C = 0”
then
• the FSO module sets OA_Req_S = 1.
22
Safe (User
acknowledgement
request)
Operational
OA_C
(positive edge) was set by the PROFIsafe
F-Host for the FSO module.
23
Safe (User
acknowledgement
request)
Safe (Module
passivation
with a
command)
Command “activate_FV_C = 1” was sent from the
PROFIsafe F-Host.
ID
From
To
Description
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...