![ABB FSO-21 Скачать руководство пользователя страница 60](http://html.mh-extra.com/html/abb/fso-21/fso-21_user-manual_2728060.webp)
60 Safety functions
SSM
• SSM indication goes on when the motor speed is in the user-defined range. The
FSO module switches off the indication when the monitored speed exceeds the
configured limit.
SDI
• SDI active state is indicated when the motor rotates in the correct direction. The
FSO module switches off the indication when the function is acknowledged or the
rotation direction changes to the forbidden direction (this also causes the SDI to
trip, that is, the FSO module activates the SSE function).
For further information on indication and output parameters, see chapter
on page
, and
.
FSO modes
The FSO can be in one of the following modes:
•
Power down:
The power to the FSO is off. The drive STO circuit is open. The
POWER LED is off.
•
Start-up
: The FSO is starting up after power-up. Indicated with a blinking green
RUN LED.
•
Running
: The FSO is up and running. It can be in different states (see section
on page
) depending on the status of safety functions and the
safety fieldbus communication. Indicated with a green RUN LED.
•
Fail-safe
: There is a failure in the FSO. The drive STO is active. Indicated with a
red STATUS/FAULT LED. You have to reboot the FSO to exit the Fail-safe mode.
See section
Transitions between FSO modes and states
•
Configuration
: Parameters are uploaded from the FSO module. The drive STO
is active. Indicated with blinking RUN and STATUS/FAULT LEDs. You can exit the
Configuration mode by downloading the new configuration to the FSO or by
rebooting the FSO.
For more information on the FSO LEDs, see section
.
FSO states
When the FSO is up and running, it can be in one of the following states depending
on the drive STO status:
•
Safe
: STO active, that is, the drive STO circuit is open and the motor is stopped.
The SBC is active (if used).
•
Operational
: STO inactive.
In the Operational and Safe states, the FSO can execute the safety functions.
Note
: When the POUS function is active, the FSO module is in the Operational state
and the drive STO is active.
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...