Parameter
Value
Current consumption from 24 V DC power supply at
the L+/UP and M/ZP terminals of the CPU/commu-
nication interface module
Ca. 5 mA
Galvanic isolation
Yes, between the input group and the
output group and the rest of the module
Isolated groups
3 groups (1 group for 8 input channels, 2
groups for 8 output channels)
Surge-voltage (max.)
35 V DC for 0.5 s
Max. power dissipation within the module
2.3 W
Weight
Ca. 150 g
Mounting position
Horizontal or vertical
Cooling
The natural convection cooling must not
be hindered by cable ducts or other parts
in the switchgear cabinet.
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is
protected individually by an external fuse.
Technical data of the digital inputs
Parameter
Value
Number of channels per module
8
Distribution of the channels into
groups
1 group for 8 channels
Connections of the channels I0 to I7 Terminals 2 to 9
Reference potential for the channels
I0 to I7
Terminal 1
Indication of the input signals
1 yellow LED per channel; the LED is ON when the
input signal is high (signal 1)
Monitoring point of input indicator
LED is part of the input circuitry
Input type according to EN 61131-2
Type 1 source
Type 1 sink
Type 1 AC
1
)
Input signal range
-24 V DC
+24 V DC
24 V AC 50/60 Hz
Signal 0
-5 V...+3 V
-3 V...+5 V
0 V AC...5 V AC
Undefined signal
-15 V...+ 5 V
+5 V...+15 V
5 V AC...14 V AC
Signal 1
-30 V...-15 V
+15 V...+30 V
14 V AC...27 V AC
Input current per channel
Input voltage 24 V
Typ. 5 mA
Typ. 5 mA r.m.s.
Input voltage 5 V
Typ. 1 mA
Typ. 1 mA r.m.s.
Input voltage 14 V
Typ. 2.7 mA r.m.s.
Input voltage 15 V
> 2.5 mA
Input voltage 27 V
Typ. 5.5 mA r.m.s.
Input voltage 30 V
< 8 mA
Max. permissible leakage current (at
2-wire proximity switches)
1 mA
Typ. 1 mA r.m.s.
No effects of
multiple over-
loads
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US
266