With "Module" the following allocation applies depending on the master:
Module error: I/O bus or PNIO: 31 = module itself; COM1/COM2: 1...10 =
expansion 1...10
Channel error: I/O bus or PNIO = module type (1 = AI); COM1/COM2:
1...10 = expansion 1..10
4
)
In case of module errors, with channel "31 = Module itself" is output.
State LEDs
LED
State
Color
LED = OFF
LED = ON
LED flashes
PWR
Process
voltage
24 V DC via
terminal
Green CPU module
voltage or
external
24 V DC
supply voltage
is missing
3.3 V system
voltage (I/O
bus) and
external
24 V DC supply
voltage are
present
---
ERR
Channel or
module error
Red
No error or
process
voltage is
missing
Severe error in
the module
Error on 1 or
more chan-
nels of the
module
Measuring ranges
Risk of invalid analog input values!
The analog input values may be invalid if the measuring range of the inputs is
exceeded.
Make sure that the analog signal at the connection terminals is always within
the signal range.
Range
-2.5 ...
+2.5 V
-5 ... +5
V
0 ... 5 V
0 ... 10 V 0 ... 20
mA
4 ... 20
mA
Digital value
Decimal Hex.
Overflow >2.9397 >5.8795 >5.8795 >11.758
9
>23.517
8
>22.814
2
32767
7FFF
Meas-
ured
value too
high
2.9397
:
2.5014
5.8795
:
5.0029
5.8795
:
:
:
5.0015
11.7589
:
:
:
10.0029
23.5178
:
:
:
20.0058
22.8142
:
:
20.0058
32511
:
27664
27658
27656
7EFF
:
6C10
6C0A
6C08
Normal
range
2.5000
:
0.0014
5.0000
:
0.0029
5.0000
:
:
:
0.0015
10.0000
:
:
:
0.0029
20.0000
:
:
:
0.0058
20.0000
:
:
4.0058
27648
:
16
10
8
6C00
:
0010
000A
0008
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US