Name
Value
Internal value
Internal value,
type
Default
Behaviour DO at
comm. error
1
)
Off
Last value
Last value 5 sec
Last value 10 sec
Substitute value
Substitute value
5 sec
Substitute value
10 sec
0
1
6
11
2
7
12
BYTE
Off
0x00
Substitute value
at output
0...255
00h...FFh
BYTE
0
0x0000
Detect voltage
overflow at out-
puts
2
)
Off
On
0
1
BYTE
On
0x01
1
) The parameters Behaviour DO at comm. error is only analyzed if the Failsafe-mode is ON.
2
) The state "externally voltage detected" appears, if the output of a channel DC0...DC7 should
be switched on while an externally voltage is connected
Chapter 1.7.5.2.3 “Connections”
. In this case the start up is disabled, as long as the externally voltage is con-
nected. The monitoring of this state and the resulting diagnosis message can be disabled by
setting the parameters to "OFF".
1.7.5.2.8 Diagnosis and state LEDs
Structure of the diagnosis block via PNIO_DEV_ALARM function block
Byte Number
Description
Possible Values
1
Diagnosis Byte, slot number 31 = CI501-PNIO (e. g. error at inte-
grated 8 DI / 8 DO)
1 = 1st connected S500 I/O module
...
10 = 10th connected S500 I/O module
2
Diagnosis Byte, module
number
According to the I/O bus specification
passed on by modules to the fieldbus
master
3
Diagnosis Byte, channel
According to the I/O bus specification
passed on by modules to the fieldbus
master
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/31
3ADR010278, 3, en_US
821