Parameter
Value
Input signal range
0 V AC...265 V AC
Input signal frequency
47 Hz...63 Hz
Input characteristic
According EN 61132-2 Type 2
Signal 0
0 V AC...40 V AC
Undefined signal
> 40 V AC...< 74 V AC
Signal 1
74 V AC...265 V AC
Input current per channel
Input voltage = 159 V AC
> 7 mA
Input voltage = 40 V AC
< 5 mA
Overvoltage protection
Yes
Max. cable length
Shielded
1000 m
Unshielded
600 m
Technical data of the relay outputs
Parameter
Value
Number of channels per module
4 relay outputs
Distribution of channels into groups
4 groups of 1 channel each
Connection of the four relays
Chapter 1.6.1.2.8.3 “Connections”
Galvanic isolation
Between the channels and from the rest of the
module
Indication of the output signals
1 yellow LED per channel, the LED is ON when
the relay coil is energized
Monitoring point of output indicator
LED is controlled by process CPU
Way of operation
Non-latching type
Output delay (0->1 or 1->0)
On request
Relay power supply
By UP process supply voltage
Relay outputs
Output short circuit protection
Must be provided externally with a fuse or cir-
cuit breaker
Rated protection fuse
6 A gL/gG per channel
Output switching capacity
Resistive load, max.
3 A; 3 A (230 V AC), 2 A (24 V DC)
Inductive load, max.
1.5 A; 1.5 A (230 V AC), 1.5 A (24 V DC)
Lamp load
60 W (230 V AC), 10 W (24 V DC)
Lifetime (cycles)
Mechanical: 300 000;
Under load: 300 000 (24 V DC at 2 A), 200 000
(120 V AC at 2 A), 100 000 (230 V AC at 3 A)
Spark suppression with inductive AC load
Must be performed externally according to
driven load specifications
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US