Technical data
The System Data of AC500-eCo apply
Chapter 2.5.1 “System data AC500-eCo V3”
Only additional details are therefore documented below.
Parameter
Value
Process supply voltage UP
Connections
Terminal 19 for UP (+24 V DC) and terminal 20
for ZP (0 V DC)
Rated value
24 V DC
Current consumption via UP terminal
20 mA + max. 0.5 A per output
Max. ripple
5 %
Inrush current
0.000002 A
2
s
Protection against reversed voltage
Yes
Rated protection fuse for UP
Recommended; the outputs must be protected
by an 3 A fast-acting fuse
Current consumption from 24 V DC power
supply at the L+/UP and M/ZP terminals of
the CPU/communication interface module
Ca. 10 mA
Galvanic isolation
Yes, between the output group and the rest of
the module
Isolated groups
1 (16 channels per group)
Surge-voltage (max.)
35 V DC for 0.5 s
Max. power dissipation within the module
1.4 W
Weight
Ca. 125 g
Mounting position
Horizontal or vertical
Cooling
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is
protected individually by an external fuse.
Technical data of the digital outputs
Parameter
Value
Number of channels per module
16 transistor outputs (24 V DC, 0.5 A max.)
Distribution of the channels into groups
1 (16 channels per group)
Connection of the channels O0 to O7
Terminals 1 to 9
Connection of the channels O8 to O15
Terminals 11 to 18
Common power supply voltage
Terminal 19 (positive pole of the process voltage,
signal name UP)
Reference potential for the channels O0 to
O15
Terminal 20 (negative pole of the process
voltage, signal name ZP)
No effects of
multiple over-
loads
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US
209