Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Technical data of the module
Parameter
Value
Process supply voltages UP/UP3
Rated value
24 V DC (for inputs and outputs)
Max. load for the terminals
10 A
Protection against reversed voltage
Yes
Rated protection fuse on UP/UP3
10 A fast
Galvanic isolation
Ethernet interface against the rest of the
module
Inrush current from UP (at power up)
On request
Current consumption via UP (normal
operation)
0.15 A
Current consumption via UP3
0.06 A + 0.5 A max. per output
Connections
Terminals 1.8 and 2.8 for +24 V (UP)
Terminal 3.8 for +24 V (UP3)
Terminals 1.9, 2.9 and 3.9 for 0 V (ZP)
Max. power dissipation within the module
6 W
Number of digital inputs
8
Number of digital outputs
8
Number of configurable digital inputs/outputs 8
Input data length
12 bytes
Output data length
20 bytes
Reference potential for all digital inputs and
outputs
Negative pole of the supply voltage, signal
name ZP
Setting of the I/O device identifier
With 2 rotary switches at the front side of the
module
Diagnosis
1.7.5.3.8 “Diagnosis” on page 848
Operation and error displays
34 LEDs (totally)
Weight (without terminal unit)
Ca. 125 g
Mounting position
Horizontal or vertical with derating (output load
reduced to 50 % at 40 °C per group)
Extended ambient temperature (XC version) > 60 °C on request
Cooling
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/31
3ADR010278, 3, en_US
855