2
)
Setting
Description
On +Failsafe
Error LED lights up at errors of all error
classes, Failsafe mode on *)
Off by E4 + Failsafe
Error LED lights up at errors of error
classes E1, E2 and E3, Failsafe mode on
*)
Off by E3 + Failsafe
Error LED lights up at errors of error
classes E1 and E2, Failsafe mode on *)
1
) With a faulty ID, the module reports a "parameter error" and does not perform cyclic process
data transmission
2
) For a description of the counter operating modes, please refer to the 'Fast Counter' section
Chapter 1.6.1.2.9 “Fast counter” on page 349
3
) With CS31 without the parameter "Fast Counter"
The fast counter of the module does not work if the module is connected to a
CS31 bus module.
5
) The parameter Behavior outputs at comm. error is only analyzed if the Failsafe mode is ON.
Group parameters for the digital part
Name
Value
Internal value Internal
value, type
Default
EDS Slot /
Index
Input delay
0.1 ms
1 ms
8 ms
32 ms
0
1
2
3
BYTE
0.1 ms
0x00
0x0Y05
Detect short
circuit at out-
puts
Off
On
0
1
BYTE
On
0x01
0x0Y06
Substitute
value at
output
0...255
00h...FFh
BYTE
0
0x0000
0x0Y08
*) The parameters Behavior DO at comm. error is only analyzed if the Failsafe mode is ON.
Group parameters for the analog part
Name
Value
Internal value Internal
value, type
Default
EDS Slot /
Index
Analog data
format
Standard
Reserved
0
255
BYTE
0
0x0Y04
*) The parameter Behaviour AO at comm. error is only analyzed if the Failsafe mode is ON.
Device specifications
I/O modules > Digital/Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
600