Number of cores
per terminal
Conductor type
Cross section
Stripped conductor
end
1
solid
0.2 mm
²
to 2.5 mm
²
10 mm
1
flexible
0.2 mm
²
to 2.5 mm
²
10 mm
1 with wire-end fer-
rule (without plastic
sleeve)
flexible
0.25 mm
²
to 2.5 mm
²
10 mm
1 with wire-end fer-
rule (with plastic
sleeve)
flexible
0.25 mm
²
to 2.5 mm
²
10 mm
2.6.4.6
CANopen field bus
For CANopen, only bus cables with characteristics as recommended in ISO 11898 are to be
used. The requirements for the bus cables depend on the length of the bus segment. Regarding
this, the following recommendations are given by ISO 11898:
Length of seg-
ment [m]
Bus cable (shielded, twisted pair)
Max. transmis-
sion rate [kbit/s]
Conductor
cross section
[mm
²
]
Line resistance
[
W
/km]
Wave impe-
dance [
W
]
0...40
0.25...0.34 /
AWG23, AWG22
70
120
1000 at 40 m
40...300
0.34...0.60 /
AWG22, AWG20
< 60
120
< 500 at 100 m
300...600
0.50...0.60 /
AWG20
< 40
120
< 100 at 500 m
600...1000
0.75...0.80 /
AWG18
< 26
120
< 50 at 1000 m
NOTICE!
Risk of telegram and data errors!
The use of wrong cable type and quality could lead to limitations in cable length,
causing telegram and data errors.
NOTICE!
Risk of damaging the terminating resistor!
A bus-line short-circuit to the 24 V DC power supply can cause damage by
exceeding the power rating of the terminating resistor.
Terminal type:
Spring terminal
Types of bus
cables
System assembly, construction and connection
AC500 (Standard) > Connection and wiring
2022/01/31
3ADR010278, 3, en_US
995