Range
Pt100
-50 ...
+70 °C
1
)
Pt100 /
Pt1000
-50 ...
+400 °C
Pt100
-200 ...
+850 °C
Ni1000
-50 ...
+150 °C
Cu50
-200 ...
+200 °C
Digital value
Decimal
Hex.
Measured
value too
low
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-501
:
-600
FE0B
:
FDA8
Under-
flow
< -60.0
°C
< -60.0
°C
< -200 °C < -60.0
°C
< -200 °C
2
)
-32768
8000
1
) also possible with resolution 0.01 K
2
) if Cu50 with 1.426, -50 °C is valid; if Cu50 with 1.428, -200.0 °C is valid
Resistor input range
The represented resolution corresponds to 16 bits.
Range
Resistor [
W
]
Digital value
Decimal
Hex.
Overflow
> 55000
32767
7FFF
Measured value
too high
55000
:
50001
30413
:
27649
76CD
:
6C01
Normal range
50000
:
2
1
0
27648
:
1
1
0
6C00
:
0001
0001
0000
Thermocouple input ranges
The represented resolution corresponds to 16 bits.
Range
Typ J
-210 ...
+1200 °C
Typ K
-270 ...
+1372 °C
Typ N
-270 ...
+1300 °C
Typ S
-50 ...
+1768 °C
Typ T
-270 ...
+400 °C
Digital value
Decimal
Hex.
Overflow
> 1200.0
°C
> 1372.0
°C
> 1300.0
°C
> 1768.0
°C
> 400.0
°C
32767
7FFF
Normal
range
1768.0 °C
17680
4510
1372.0 °C
:
13720
3598
:
1300.0 °C :
13000
32C8
1200.0 °C :
:
:
12000
2EE0
:
:
:
:
400.0 °C
4000
0FA0
:
:
:
:
:
:
:
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
481